ADCP-80-575
Issue 2
December 2006
1388844 Rev B
PowerWorx
®
Power Distribution Products
Select Series™ Fuse Platform (With
Enhanced KLM Fuses) User Manual
18858-A
Przeglądanie stron 0
1 2 3 4 5 6 ... 39 40

Podsumowanie treści

Strona 1 - Power Distribution Products

ADCP-80-575Issue 2December 20061388844 Rev BPowerWorx® Power Distribution ProductsSelect Series™ Fuse Platform (WithEnhanced KLM Fuses) User Manual188

Strona 2 - DISCLAIMER OF LIABILITY

ADCP-80-575 • Issue 2 • December 2006Page 4© 2006, ADC Telecommunications, Inc.1.4 Packaged HardwareThe fuse platform is shipped with hardware compone

Strona 3 - TABLE OF CONTENTS

ADCP-80-575 • Issue 2 • December 2006Page 5© 2006, ADC Telecommunications, Inc.Figure 2. Packaged Hardware ComponentsREAR COVER FOR OUTPUT POWER TERMI

Strona 4

ADCP-80-575 • Issue 2 • December 2006Page 6© 2006, ADC Telecommunications, Inc.1.5 AccessoriesThe following accessories are available for the fuse pla

Strona 5 - GENERAL SAFETY PRECAUTIONS

ADCP-80-575 • Issue 2 • December 2006Page 7© 2006, ADC Telecommunications, Inc.Figure 3. Block Diagram of GMT-KLM Bus– Initially, if there is no input

Strona 6

ADCP-80-575 • Issue 2 • December 2006Page 8© 2006, ADC Telecommunications, Inc.– An alarm can be cleared in any KLM fuse position by installing a new

Strona 7 - 1.2 Fuse Platform Components

ADCP-80-575 • Issue 2 • December 2006Page 9© 2006, ADC Telecommunications, Inc.Each input terminal block includes two pairs of 0.25-inch studs that ar

Strona 8 - FRONT VIEW

ADCP-80-575 • Issue 2 • December 2006Page 10© 2006, ADC Telecommunications, Inc.1.12 Ground ConnectorsTwo #10 studs (with nuts) are provided for groun

Strona 9 - 1.3 Product Options

ADCP-80-575 • Issue 2 • December 2006Page 11© 2006, ADC Telecommunications, Inc.alarm indicator is off when all fuses in the fuse holder module are op

Strona 10 - 1.4 Packaged Hardware

ADCP-80-575 • Issue 2 • December 2006Page 12© 2006, ADC Telecommunications, Inc.1.18 Voltage Designation LabelA voltage designation label, shown in Fi

Strona 11

ADCP-80-575 • Issue 2 • December 2006Page 13© 2006, ADC Telecommunications, Inc.inches (4.45 cm) of air space (one rack space) must be provided above

Strona 12 - 1.7 Power Buses

ADCP-80-575 • Issue 2 • December 2006 • PrefacePage iiCOPYRIGHT© 2006, ADC Telecommunications, Inc.All Rights ReservedPrinted in the U.S.A.REVISION HI

Strona 13

ADCP-80-575 • Issue 2 • December 2006Page 14© 2006, ADC Telecommunications, Inc.2 UNPACKING AND INSPECTIONBefore starting the installation, always ope

Strona 14 - 1.10 Input Power Connectors

ADCP-80-575 • Issue 2 • December 2006Page 15© 2006, ADC Telecommunications, Inc.3.3 Materials RequiredThe following materials are required to install

Strona 15 - 1.11 Output Power Connectors

ADCP-80-575 • Issue 2 • December 2006Page 16© 2006, ADC Telecommunications, Inc.3. Re-install the fuse holder (with working fuse).4. Connect one test

Strona 16 - 1.15 Fuse Alarm Indicators

ADCP-80-575 • Issue 2 • December 2006Page 17© 2006, ADC Telecommunications, Inc.4. Repeat the test procedure for second fuse type, if present.5. Repea

Strona 17 - (5.99 CM)

ADCP-80-575 • Issue 2 • December 2006Page 18© 2006, ADC Telecommunications, Inc. 4.1 Installing Cable Management Bar (Optional I

Strona 18 - 1.21 Cooling

ADCP-80-575 • Issue 2 • December 2006Page 19© 2006, ADC Telecommunications, Inc.4.2 Mounting Fuse Platform on RackThe fuse platform can be mounted in

Strona 19 - 1.24 Dimensions

ADCP-80-575 • Issue 2 • December 2006Page 20© 2006, ADC Telecommunications, Inc.4. Place the fuse platform in the specified mounting space within the

Strona 20 - 3 PRE-INSTALLATION

ADCP-80-575 • Issue 2 • December 2006Page 21© 2006, ADC Telecommunications, Inc.6. Locate the C GND (chassis ground) studs at the rear of the panel as

Strona 21 - 3.4 Continuity Tests

ADCP-80-575 • Issue 2 • December 2006Page 22© 2006, ADC Telecommunications, Inc.Figure 16. Alarm Contact Connections 4.5 Connecting Output PowerOutpu

Strona 22

ADCP-80-575 • Issue 2 • December 2006Page 23© 2006, ADC Telecommunications, Inc.Figure 17. Output Power Connections4.6 Connecting Input PowerInput pow

Strona 23

ADCP-80-575 • Issue 2 • December 2006 • PrefacePage iii© 2006, ADC Telecommunications, Inc.TABLE OF CONTENTSContent PageAbout This Manual . . . . . .

Strona 24 -

ADCP-80-575 • Issue 2 • December 2006Page 24© 2006, ADC Telecommunications, Inc. Use the following procedure to connect the input power cables to the

Strona 25

ADCP-80-575 • Issue 2 • December 2006Page 25b. Return wires: Connect to RTN (+) terminals on the A and B input power terminalblocks. 9. Use a torque w

Strona 26

ADCP-80-575 • Issue 2 • December 2006Page 26© 2006, ADC Telecommunications, Inc.4.8 Installing GMT Fuse Designation PinsColor-coded fuse designation p

Strona 27

ADCP-80-575 • Issue 2 • December 2006Page 27© 2006, ADC Telecommunications, Inc.6. Using a multimeter set to measure DC voltage, measure the voltage b

Strona 28 - WIRE-WRAP PIN TERMINAL BLOCK

ADCP-80-575 • Issue 2 • December 2006Page 28© 2006, ADC Telecommunications, Inc. To test the KLM fuse alarm indicator, use the following procedure:1.

Strona 29

ADCP-80-575 • Issue 2 • December 2006Page 29© 2006, ADC Telecommunications, Inc.2. Wait about ten seconds until the green LED starts to blink off and

Strona 30

ADCP-80-575 • Issue 2 • December 2006Page 30© 2006, ADC Telecommunications, Inc.8 CUSTOMER INFORMATION AND ASSISTANCE© 2006, ADC Telecommunications, I

Strona 31 - (3.6 NEWTON METERS) OF TORQUE

ADCP-80-575 • Issue 2 • December 2006Page 31© 2006, ADC Telecommunications, Inc.APPENDIX A: ALLOWABLE AMPACITIES OF INSULATED CONDUCTORSThis appendix

Strona 32

ADCP-80-575 • Issue 2 • December 2006Page 32© 2006, ADC Telecommunications, Inc.* Unless otherwise specifically permitted in the code, as defined in t

Strona 34 - 6 OPERATION

ADCP-80-575 • Issue 2 • December 2006 • PrefacePage iv© 2006, ADC Telecommunications, Inc.TABLE OF CONTENTSContent Page4.6 Connecting Input Power . .

Strona 36 - Italy: 0800 782374

ADCP-80-575 • Issue 2 • December 2006 • PrefacePage v© 2006, ADC Telecommunications, Inc.ABOUT THIS MANUALThis manual describes the PowerWorx® Select

Strona 37

ADCP-80-575 • Issue 2 • December 2006 • PrefacePage vi© 2006, ADC Telecommunications, Inc.Warning: Wet conditions increase the potential for receivin

Strona 38

ADCP-80-575 • Issue 2 • December 2006Page 1© 2006, ADC Telecommunications, Inc.1 PRODUCT DESCRIPTIONThis section describes the PowerWorx Select Series

Strona 39

ADCP-80-575 • Issue 2 • December 2006Page 2© 2006, ADC Telecommunications, Inc.Figure 1. Dual Bus KLM-GMT Fuse Platform18877-BPROTECTIVECOVERREAR VI

Strona 40

ADCP-80-575 • Issue 2 • December 2006Page 3© 2006, ADC Telecommunications, Inc. Depending on customer order, the fuse platform may have one fuse type